Step 3 Press ENTER when the normal screen is displayed to go to the password input
screen. Press ← and → to select the digit that you need to enter. Press ↑ and ↓ to
modify the value. Then, press ENTER to confirm what you have entered.
Step 4 Choose Set Point on the main menu, and set the cooling threshold and cooling
hysteresis.
----End

9.3 Commissioning Monitoring Components

9.3.1 Preparations and WebUI Login

Prerequisites
Procedure
Step 1 Connect a network cable between the PC network port and the WAN1 port
(protected by a security mechanism) on the ECC800-Pro.
Table 9-6 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
WAN1
Issue 03 (2022-12-15)
NO TE
● Self-test
The internal fan operates for 30 seconds.
The compressor and the external fan operate for 3 minutes.
The compressor and the external fan stop.
The smart cooling product operates properly based on the normal logic.
● Running properly
After the self-test of the smart cooling product is successful, it starts to operate
properly. In this case, the internal fan operates. If the temperature of the internal
fan reaches the threshold of starting cooling, the cooling system operates, and the
compressor and external fan operate.
NO TE
The initial password is 0001.
NO TE
● Cooling threshold: 30°C.
● Cooling hysteresis: 5°C.
Computer operating system: Support Windows 7 and later versions
It is recommended that the screen resolution be 1366 x 768 or higher.
Browser: IE11 and later versions; Firefox and later versions; Chrome and later
versions
Copyright © Huawei Digital Power Technologies Co., Ltd.
9 Commissioning Core Components
Default IP Address
192.168.8.10
71