4.7.3.2 Setting the Transparent Transmission Function for the ECC800-Pro
Collector
Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > NMS Application > Transparent Transmission
Channel.
Step 3 Set COM2(Port:3212) to Enable and click Submit.
Mapping relationship: COM1 corresponds to port 3211, COM2 port 3212, COM3 port 3213, and
COM4 port 3214.
Step 4 Log in to the NetEco WebUI as an administrator.
Step 5 Choose System > Service Settings > Data Center Planning. The Data Center
Planning page is displayed.
Step 6 Select the management domain to add a device.
Step 7 (Optional) If the management domain is a rack, click the management domain
and choose Design under
Otherwise, skip this step.
Issue 01 (2021-04-20)
Using the transparent transmission function, the NMS can directly manage
southbound components that are not monitored by the ECC800-Pro.
A device connected to the COM port on the ECC800-Pro or UIM20A expansion
module can be connected to the NetEco using the transparent transmission
function.
In this example, the COM2 port of the ECC800-Pro is used for transparent
transmission.
NO TE
If the port is set for the first time, you are prompted to set an authentication
password. On the Set Authentication Password tab page, set
Authentication password and Confirm authentication password and click
Submit.
NO TE
Enable Security Authentication is set to Enable by default. If so, an authentication
password must be set. If Enable Security Authentication is set to Disable, there is no
need to set an authentication password but this is risky.
If the port has been used, you will be prompted that the transparent
transmission function cannot be enabled and you need to select an idle port.
NO TE
● Ensure that the ECC800-Pro connected to the device has been synchronized to the
NetEco.
● Ensure that the management domain to add the device is the management domain or
sub-management domain of the ECC800-Pro.
Copyright © Huawei Technologies Co., Ltd.
. The page for adding a device is displayed.