Huawei FusionDC1000A Commissioning Manual page 35

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario)
Figure 4-1 Settings Wizard
Table 4-3 System Param.
Item
Battery cabinet
quantity
Pooling
Charging mode
Issue 01 (2021-04-20)
Description
Total number of battery
cabinets.
If this parameter is set to
Enable, the system allows
battery pooling.
Currently, the system does
not support pooling. Retain
the default value Disable.
Mode 1 can meet the
requirements of most
customers.
Mode 2 meets the
requirements for charging
batteries immediately after
discharging is complete at a
high temperature.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning Core Devices
Default
Value Range
Value
1
1–15
Disable
Disable, Enable
Mode 1
Mode 1, Mode 2
29