4.1.2.2 Starting the Inverter
UPS System User List
Table 4-1 UPS system user list
Default User
admin (administrator)
operator (common user)
Starting the UPS on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
4.1.2.3 Powering On Loads
After the inverter starts, the UPS works in normal mode. The Bypass mode alarm
disappears. Check that the UPS has transferred to normal mode by viewing the
system running status diagram.
Procedure
Step 1 After confirming that the battery strings are properly connected, turn on the
battery string input switch. If there are multiple battery strings, turn on the switch
for each battery string and then the general switch between battery strings and
the UPS. After you turn on the battery string input switch, the No battery alarm
disappears.
Step 2 Turn on the UPS output circuit breaker QF3.
After the UPS is started for the first time, perform a battery capacity test to ensure
that battery parameters are correctly displayed.
Step 3 (Optional) Turn on the lighting output circuit breaker on the integrated UPS and
check whether the PWR indicator on the AC actuator lights up. Press down the
lighting button to power on the light.
Step 4 Turn on the smart cooling product circuit breaker on the integrated UPS to power
on the smart cooling products.
Issue 01 (2021-04-20)
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
NO TICE