Huawei FusionDC1000A Commissioning Manual page 71

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario)
2.
Issue 01 (2021-04-20)
Figure 5-14 Opening the cover
Press the test button on the pneumatic switch to short-circuit the cables
inside to simulate an extinguishant release.
Figure 5-15 Pneumatic switch
NO TE
– The extinguishant control panel generates a LOCAL FIRE alarm, and Extinguishant
Release indicator turns on. The warning sign is steady on.
– LOCAL FIRE terminal generates a LOCAL FIRE alarm signal.
Copyright © Huawei Technologies Co., Ltd.
5 System Commissioning
65