Step 3 Unlock the keyboard.
The keyboard is locked to prevent misoperation.
Step 4 Set the time displayed on the fire alarm control panel.
Choose System Setting > Time Setting, enter the correct date and time, and click
OK. The system saves the time you have set.
----End

4.5.2 Commissioning the Emergency Light (Standard)

Prerequisites
The sockets of the emergency light have been powered on.
Preparations
Tools: step ladder, Phillips screwdriver
Documents: power supply and distribution system diagram, fire extinguishing
device layout diagram (standard)
Skill requirement: fire engineer
Procedure
Step 1 Press the emergency light test button and check whether the emergency light
enters the working mode.
Issue 01 (2021-04-20)
NO TE
If the power indicator is on and other indicators are off, the power-on process succeeds. If a
yellow fault indicator is on, rectify the fault before continuing follow-up operations.
To unlock the keyboard, press Keyboard and then enter the password (the
initial password is 111111).
To lock the keyboard, press Keyboard when the keyboard is unlocked.
The keyboard will be locked if no operation is performed within 5 minutes.
NO TE
For the diagrams, see the initial configuration parameter manual for the solution in use.