FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Follow-up Procedure
After the alarm is cleared, you need to manually close the door. After the door is
closed, the door open alarm is cleared.
5.3.11 (Optional) NetEco Management
5.3.11.1 Data Center Management
5.3.11.1.1 Connecting a Communications Cable
Procedure
Step 1 Connect a communications cable to the WAN1 port on the ECC800-Pro.
Figure 5-16 Connecting a communications cable
----End
5.3.11.1.2 Setting NetEco Parameters
Procedure
Step 1 Apply for a fixed IP address to the equipment room network administrator.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 5-18 IP parameters
Path
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
Issue 02 (2021-06-30)
Parameter
Default
Value
IP
192.168.8.1
0
Subnet
255.255.25
mask
5.0
Default
192.168.8.1
gateway
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Setting
Set this parameter based on the IP
address assigned by the network
administrator.
Set this parameter based on the
subnet mask assigned by the network
administrator.
Set this parameter based on the
default gateway address assigned by
the network administrator.
139