Commissioning The Electrode Water Sensor - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Step 3 Check the function of the T/H sensor.
Table 5-10 Function check
Check Method
Check the running
information about the T/H
sensor on the WebUI.
Set T/H sensor alarm
thresholds.
----End

5.3.7.3 Commissioning the Electrode Water Sensor

Prerequisites
One end of the network cable has been stripped, core wires 7 and 8 have been
connected to the cable delivered with the electrode water sensor, and the other
end of the network cable has been connected to the AI/DI port on the rack
environment unit.
Context
Issue 02 (2021-06-30)
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
To use the AI/DI sensor, enable the corresponding AI/DI port and name the
sensor. The specific alarm then can be reported.
If the sensor is prefabricated, only check its settings.
The actual value may vary. Only the method of the parameter settings is
described.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Info, and view the
current cabinet temperature and humidity.
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Parameters and set
High temperature alarm threshold, Low
temperature alarm threshold, High humidity
alarm threshold, and Low humidity alarm
threshold as required.
NOTE
The default values of High temperature alarm
threshold, Low temperature alarm threshold, High
humidity alarm threshold, and Low humidity alarm
threshold for the cold aisle are 35.0°C, 5.0°C, 85.0%
RH, and 15.0% RH respectively. The default values of
High temperature alarm threshold, Low
temperature alarm threshold, High humidity alarm
threshold, and Low humidity alarm threshold for
the hot aisle are 45.0°C, 10.0°C, 85.0% RH, and
15.0% RH, respectively. The cold and hot aisles can be
determined based on the DIP switch settings of the
T/H sensors.
5 Power-On Commissioning
122