Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Maintenance
Area
Camera
Intelligent lithium
battery
monitoring system
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Camera
On the ECC800-
availability
Pro WebUI,
choose
Maintenance >
Manage Video >
Video Info to
enter the video
view page. Type
the camera name
or IP address to
find the camera,
and click View to
view the real-
time monitoring
page.
Battery
-
management
alarm
Cleanliness
-
Battery
-
connection
Measurement of
-
the ambient
temperature of
the intelligent
battery
monitoring system
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
The monitoring
If the
page is properly
monitoring
displayed after
page is not
you click View.
displayed after
you click View,
check that the
IP address is
correctly set,
and check cable
connections or
replace the
camera. For
details, see
6.4.3.5
Replacing a
Camera.
No battery
Identify the
management
cause of an
alarm is
alarm based on
generated.
the alarm
information.
Wipe the battery
Remove dust.
surface using a
piece of white
paper and the
paper does not
turn black.
Battery terminals
Locate poor
and cables are in
contact points
good contact.
between battery
terminals and
cables.
The ambient
Locate the
temperature of
cause of an
the intelligent
abnormal
battery
temperature.
monitoring
system is lower
than 45°C.
6 O&M
170

Advertisement

Table of Contents
loading