Installing Remote T/H Sensors For The Smart Cooling Product; Installing T/H Sensors - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
If the PAD screen needs to remain on for a long time during usage, adjust the
brightness to below 80%.
----End

4.2.6.3 Installing Remote T/H Sensors for the Smart Cooling Product

Procedure
Step 1 Install T/H sensors.
1.
2.
Step 2 Set the DIP switch address of the T/H sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.
Table 4-5 DIP switch settings on T/H sensors
Address
1
2
The default address of T/H sensors purchased from Huawei is 1.
Step 3 Insert the pre-routed cables into the ports on the T/H sensors on the front and
rear doors.
----End

4.2.6.4 Installing T/H Sensors

Procedure
Step 1 Install T/H sensors.
1.
Issue 02 (2021-06-30)
NO TICE
Open the front and rear doors of the cabinet.
Unpack the two T/H sensors, and attach one to the 33 U position on the right
post of the front door and the other to the 11 U position on the right post of
the rear door of the cabinet.
NO TE
The installation positions of the T/H sensors can be adjusted as required.
DIP Switch Sequence No.
1
2
ON
OFF
OFF
ON
NO TICE
Open the front and rear doors of the cabinet.
Copyright © Huawei Technologies Co., Ltd.
3
4
OFF
OFF
OFF
OFF
4 Installation Guide
5
6
OFF
OFF
OFF
OFF
75

Advertisement

Table of Contents
loading