Commissioning A Cabinet Electronic Clasp Lock - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Procedure
Step 1 Set water sensor parameters.
1.
2.
3.
4.
5.
6.
7.
8.
Step 2 Check functions of water sensors.
Table 5-11 Function check
Check Method
Immerse the two
contacts of the
electrode water
sensor in water.
----End

5.3.8 Commissioning a Cabinet Electronic Clasp Lock

Prerequisites
The cabinet door can be opened and closed properly. If the cabinet door cannot be
opened and closed properly, adjust the position of the cabinet electronic clasp lock
by performing steps 1 and 2.
Procedure
Step 1 (Optional) Check whether the cabinet door lock is leveled to 2000 (+3) mm. If
not, adjust it.
Step 2 (Optional) If the cabinet door still cannot be opened after step 1 is performed,
adjust the position of the cabinet electronic clasp lock by using the slotted holes
until the cabinet door can be opened and closed properly.
Issue 02 (2021-06-30)
NO TE
The following describes how to connect a water sensor to the AI/DI_2 port on the ECC800-
Pro.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_2 to Leak
and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2
Port Settings.
Set Leak sensor to Enable and click Submit.
Set Leak sensor type to Leak sensor(Electroc) and click Submit.
Click Unhide All Advanced Signals, and click Power Supply Parameters.
Ensure that I power supply enable(AIDI_2/COM1/AIDI_4/COM3) is Enable.
Normal Connection Status
Leak DI alarm is generated
on the active alarm screen of
the app or on the WebUI.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
Wipe dry the two contacts of
the water sensor. The alarm
disappears automatically.