Chapter 10 Troubleshooting; Troubleshooting By Symptom - Mitsubishi Electric MELSEC iQ-R Series User Manual

C controller/c intelligent function module secs/gem communication software pre-installed model
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

10
TROUBLESHOOTING
This section explains the troubleshooting of a SECS/GEM communication software pre-installed model module.
10.1

Troubleshooting by Symptom

This section shows the troubleshooting by phenomenon for a SECS/GEM communication software pre-installed model
module.
Symptom
A multi-CPU error occurred with a
programmable controller CPU and
MELSEC-Q series SECS/GEM
communication software pre-installed
model module.
A ladder program cannot be written to
the programmable controller CPU.
The user login settings of the C
Controller module or C intelligent
function module are unknown.
C language settings cannot be written
to the C Controller module.
The SECS/GEM communication
software cannot be installed on the
personal computer.
The project file of the SECS/GEM
communication software cannot be
opened.
Check item
Do the multi-CPU settings of the
programmable controller CPU and
MELSEC-Q series SECS/GEM
communication software pre-installed
model module match?
Is there a problem with the GX
Works2 or GX Works3 settings?
Is there an error during Ethernet
diagnosis?
Has the C Controller module or C
intelligent function module been
initialized?
Is there a problem with the settings of
Setting/monitoring tools for the C
Controller module?
Does the user currently logged in
have administrative rights for the
personal computer?
Was the PC restarted after installing
the setting tool?
Corrective action
During use with a multi-CPU configuration, the settings of the parameters of
the CPU must match.
Review the parameter settings.
For the parameter setting method, see the manual of the programmable
controller CPU to be used.
When the GX Works2 or GX Works3 cannot connect with the Programmable
Controller CPU, check for problems in the settings of the GX Works2 or GX
Works3 .
For the parameter setting method, see the manual of the programmable
controller CPU to be used.
When the GX Works2 or GX Works3 and Programmable Controller CPU are
connected via Ethernet, check the details of the Ethernet diagnosis error, and
then remove the cause of the error.
The following table shows the default values when the C Controller module or
C intelligent function module has been initialized.
IP address (CH1): 192.168.3.3
Username: "target"
Password: "password"
For the initialization method, refer to the manual of the C Controller module or
C intelligent function module.
The pre-installed SECS/GEM communication software license is erased when
the C Controller module or C intelligent function module has been initialized.
When Setting/monitoring tools for the C Controller module cannot connect
with the Programmable Controller CPU, check for problems in the settings of
Setting/monitoring tools for the C Controller module.
For the configuration method, see the manual of Setting/monitoring tools for
the C Controller module.
A user with administrative rights must login and install the software.
Restart the PC after installing the setting tool.
10.1 Troubleshooting by Symptom
10 TROUBLESHOOTING
271