4.2.6.4 Installing T/H Sensors

Procedure
Step 1 Install T/H sensors.
1.
2.
Step 2 Set the DIP switch address of the T/H sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.
Table 4-6 DIP switch setting on a T/H sensor
Address
1
2
The default address of T/H sensors purchased from Huawei is 1.
Issue 01 (2020-11-30)
DIP Switch Sequence No.
1
ON
OFF
NO TICE
Open the front and rear doors of the cabinet.
Unpack the two T/H sensors and attach one sensor to the mounting bars at
the 39th U position on the front door and the other to the 37th U position on
the rear door of the cabinet.
NO TE
The installation positions of the T/H sensors can be adjusted as required.
DIP Switch Sequence No.
1
ON
OFF
NO TICE
Copyright © Huawei Technologies Co., Ltd.
2
3
OFF
OFF
ON
OFF
2
3
OFF
OFF
ON
OFF
4 Installation Guide
4
5
OFF
OFF
OFF
OFF
4
5
OFF
OFF
OFF
OFF
6
OFF
OFF
6
OFF
OFF
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule500-su61a12s

Table of Contents