Maintenance
Item
AC input
Output voltage
Indicator
Fan
Operating
environment
Monitoring
module indicator
Copyright © Huawei Technologies Co., Ltd.
Operation
-
-
-
-
-
-
Expected Result
Troubleshootin
g
Input voltage:
If the input
200–240 V AC
voltage is
abnormal, check
Frequency: 45–
the power grid
55 Hz
status and input
cable
connection.
Output voltage:
If the output
53.5 V DC±5%
voltage is
abnormal, check
the load power
and cable
connection.
The indicator on
Check the
the power
output voltage
module is steady
and determine
green.
whether the
power module
is faulty. If the
power module
is faulty, replace
it.
No abnormal
If abnormal
noise is
noise is
generated.
generated, clean
the fan.
● Ambient
If the
temperature:
temperature or
–20°C to
humidity is
+65°C
abnormal, check
the smart
● Humidity:
cooling product
0%–95% RH
status.
(non-
condensing)
The monitoring
If the indicator
module indicator
is off or any
is steady green
abnormal
or blinking
condition
green.
occurs, see
Management
System
Troubleshootin
g
fault.