Replacing A Ups2000-G - Huawei FusionModule500 V100R021C10 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Figure 6-5 Replacing a surge protection module
Step 5 Install the new surge protection module.
Step 6 Reinstall the protective panel for the SPD, and switch the SPD circuit breaker to
ON.
Step 7 Check whether there are alarms on the ECC800-Pro. If there is no alarm, the surge
protection module is functional.
----End

6.4.2.2 Replacing a UPS2000-G

Prerequisites
● Ensure that the main ground cable of the smart module is securely connected.
● After removing cables, wrap exposed terminals with insulation tape and do not
Step 1 Turn off the battery switch, or remove the wiring terminal between the battery
and the faulty UPS.
Step 2 Turn off the corresponding UPS input and output switches. Use a multimeter to
check whether the UPS input and output terminals and battery terminals are de-
energized.
Step 3 Remove the rear cover from the UPS, and remove the input and output power
cables, battery cable, and signal cable.
Wrap the exposed cable with insulation tape.
Issue 01 (2020-11-30)
Tools: electroprobe, insulation gloves, Phillips screwdriver, multimeter
Materials: A spare UPS of the same model is available and functional.
The UPS is damaged or faulty and cannot work.
NO TICE
block cable labels. If cable labels are blocked, cables may be connected
incorrectly later.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 O&M
214