Huawei FusionModule500 V100R021C10 User Manual page 124

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Saturation
Temperatu
re (°C)
7
8
9
10
11
12
13
14
15
16
17
18
● Users include admin (preset password: Changeme) and operator (preset
● If a smart cooling product is not configured with a heater or humidifier, skip
Procedure
Step 1 Log in to the ECC800 WebUI as user admin. Choose Monitoring > Cooling >
NetCol8000-A0131. The page for commissioning smart cooling products is
displayed.
Step 2 Choose Controls > Control Information, set Power on/off to ON, and click
Submit.
Issue 01 (2020-11-30)
Gauge
Pressure
(MPa)
0.9
0.93
0.96
0.99
1.02
1.05
1.09
1.12
1.16
1.19
1.23
1.27
NO TE
1 MPa ≈ 10 bar ≈ 145 psi ≈ 10.2 kgf/cm
NO TICE
password: Changeme). To enter the diagnostic mode, log in as user admin.
the commissioning steps related to the electric heater and wet film humidifier.
NO TE
If no manual operation is performed within 25 seconds after you click On, the device will
automatically run following the preset logic, and the compressor and indoor and outdoor
fans will also run according to the environment.
Copyright © Huawei Technologies Co., Ltd.
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
26
1.60
27
1.65
28
1.69
29
1.74
30
1.79
31
1.84
32
1.89
33
1.94
34
1.99
35
2.04
36
2.1
37
2.15
2
5 Power-On Commissioning
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
45
2.63
46
2.7
47
2.76
48
2.83
49
2.9
50
2.97
51
3.04
52
3.11
53
3.19
54
3.26
55
3.34
-
-
115