FusionModule500 Smart Mini Data Center
User Manual
Figure 6-3 Removing the protective panel
Step 3 Measure the L1, L2, L3, and N voltages to PE using an electroprobe, as shown in
Figure
faulty surge protection module.
Figure 6-4 Measuring voltages
Step 4 Hold the faulty surge protection module and pull it out, as shown in
During replacement, do not touch the energized components in the power
distribution subrack.
Issue 01 (2020-11-30)
6-4, and verify that the faulty SPD has no voltage before replacing the
D ANGER
Copyright © Huawei Technologies Co., Ltd.
6 O&M
Figure
6-5.