Huawei FusionModule500 V100R021C10 User Manual page 203

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Maintenance
Area
UPS
Issue 01 (2020-11-30)
Maintenance
Item
Operating
environment
LCD
Cleanliness
Parameter
configuration
Copyright © Huawei Technologies Co., Ltd.
Operation
-
-
-
-
Expected Result
Troubleshootin
g
● Ambient
● If the
temperature:
0–40°C
● Humidity:
0%–95% RH
(non-
condensing)
● If the input
According to the
If an alarm is
status icons on
present, rectify
the LCD, all units
the fault by
are operating
checking the
properly. No
device status
fault or alarm
and parameters.
information is
found in the
active and
historical alarm
records.
Wipe the cabinet
Remove the
surface using a
dust, especially
white paper and
from the air
the paper does
filter on the
not turn black.
front door, or
replace the air
filter.
The
Reset the
configuration of
parameters.
the output
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
6 O&M
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
194