Huawei FusionModule500 V100R021C10 User Manual page 122

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
3.
Step 2 Set the running parameters and control parameters for the NetCol8000-A0131 on
the WebUI.
1.
2.
3.
4.
----End
Issue 01 (2020-11-30)
Path
Parameter
Settings >
Device Type
Device
Management
Connect To
and click Add
Device.
Communicati
ons Port
Device
Address
Click Test Connect to check whether the NetCol8000-A0131 connects to the
ECC800-Pro properly.
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Cooling > NetCol8000-A0131.
On the Running Parameters tab page, set smart cooling product running
parameters.
NO TE
You are advised to set Return air temp set to 23°C, Return air humidity set to 50%
RH, and Control mode to Cold aisle average value control.
On the Controls tab page, set the smart cooling product control parameters
(such as on/off control parameters).
CA UTION
After the smart cooling product is shut down, the temperature of the smart
module increases and data running is affected. Exercise caution when
performing this operation.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Setting
Select NetCol8000-A013 from the drop-
down list box.
Select ECC800 from the drop-down list
box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the
NetCol8000-A0131 is connected to the COM3
port on the ECC800. If the NetCol8000-A013 is
connected to another port, set the number of
the connected port.
Enter the actual device address of the
NetCol8000-A0131 during operations. The
default address is 1.