Installation Environment Check - Huawei FusionModule500 V100R021C10 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
a. Pressure gauge and leather hose: dedicated for R410A. The measuring range
of the pressure gauges must be at least 4.0 MPa, and the leather hoses must
withstand a pressure of at least 4.5 MPa. Ensure that the leather pipes match
the 1/4 inch needle valves inside the unit. If necessary, prepare needle valve
adapters.
b. Dry nitrogen.
c. Nitrogen reducing valve: A reducing valve must be installed on the head of
the nitrogen cylinder, and the reducing valve range must be at least 4.0 MPa.
d. Vacuum pump airflow: 2–4 L/s; absolute vacuum: ≤ 60 Pa.
e. For equipment with humidifiers, ensure that the water pipe thread sealant
can resist temperatures higher than 85°C and the following requirements are
met:
● Applicable to all pipe materials
● Anaerobic metal pipe thread sealant with PTEF as the padding
● Maximum gap: 0.5 mm
● Pressure resistance: above 1.6 MPa
● Compliant with the industry standard JB∕T7311-2008

4.1.2 Installation Environment Check

Ensure that the installation environment meets the requirements before
installation.
Table 4-3 Installation environment checklist
Check Item
Operating
temperature
Operating
humidity
Physical
environment of
the equipment
room
Altitude
Levelness
Issue 01 (2020-11-30)
Name, Specifications, and Appearance
for the Application of Anaerobic Glue in Engineering Machinery
Specifications
Indoor operating temperature
range: 0°C to 40°C
5%–95% RH
The interior is clean and tidy,
free from dust and conductive
pollution.
0–4000 m (The power is
derated as described in IEC
62040-3 when the altitude
exceeds 1000 m.)
Allowed deviation: 3/2000 mm
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide
Technical Specification
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
58