FusionModule500 Smart Mini Data Center
User Manual
Follow-up Procedure
To modify or delete the email parameter settings, click Modify or Delete.
5.3.9 Linkage Control
Prerequisites
●
●
●
Linkage Grouping
Table 5-14 Linkage grouping
Linkage
Category
Link
emergency
ventilation
with clasp
lock open
Issue 01 (2020-11-30)
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
You have prepared a PC with an IP address in the same network segment as
that of the ECC800-Pro, and the PC is connected to the WAN_1 port on the
ECC800-Pro.
Ensure that Enable linkage control function is Yes.
Default
Status
off
Copyright © Huawei Technologies Co., Ltd.
Function
Set the linkage status to on.
● If the smart cooling product communicates
properly but does not provide the cooling function,
and the temperature in the cold aisle is greater
than or equal to the preset value (30°C by default),
the rear door of the cabinet automatically opens.
● If all smart cooling products fail to communicate,
and the temperature in the cold aisle is greater
than or equal to the preset value (30°C by default),
the rear door of the cabinet automatically opens.
● If the rear door of the cabinet is open and the
temperature in the cold aisle is higher than the
preset value (35°C by default), the front door of
the cabinet automatically opens.
5 Power-On Commissioning