FusionModule500 Smart Mini Data Center
User Manual
Table 5-10 Setting device addresses
Address
1
2
Step 4 Add the cabinet electronic clasp locks.
1.
2.
3.
4.
5.
Step 5 Commission the cabinet electronic clasp locks.
Issue 01 (2020-11-30)
Toggle
Toggle
Switch 1
Switch 2
ON
OFF
OFF
ON
Log in to the ECC800-Pro WebUI as an administrator.
Create a cabinet view in Smart Module View on the home page.
Add a cabinet electronic clasp lock.
Table 5-11 Adding a cabinet electronic clasp lock
Path
Choose System Settings
> Device Management
and click Add Device.
Click Test Connect to check whether the connection between the cabinet
electronic clasp lock and the ECC800-Pro is normal.
–
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether both are running properly, and
whether the parameter settings are consistent with the device
parameters.
Repeat
Step 4.3
and
Copyright © Huawei Technologies Co., Ltd.
Toggle
Switch 3
OFF
OFF
Parameter
Device
Attribute
Device Type
Connect To
Communicat
ions Port
Device
Address
Step 4.4
to connect other cabinet electronic clasp locks.
5 Power-On Commissioning
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
Setting
Cabinet Electronic Clasp Lock
Cabinet Electronic Clasp Lock
ECC800-Pro
COM2
Enter the actual device address of
the cabinet electronic clasp lock.
Toggle
Switch 6
OFF
OFF
131