Before using iQ Sensor Solution functions
■Setting refresh devices (network parameter)
Some iQ Sensor Solution functions cannot be performed if devices to refresh the data of remote input (RX), remote output
(RY), remote register (RWr), and remote register (RWw) are not set.
Set devices used to data refresh in advance.
For setting devices used to data refresh, refer to the following manuals.
• MELSEC-Q CC-Link System Master/Local Module User's Manual
• MELSEC-L CC-Link System Master/Local Module User's Manual
■Checking if "Read Model Name of Slave Station" is selected
The model name of a slave station can be read by selecting the "Read Model Name of Slave Station" checkbox.
Check if "Read Model Name of Slave Station" is selected in advance.
If the checkbox is not selected, write data to a CPU module in accordance with the following operating procedure before
performing an iQ Sensor Solution function.
Operating procedure
2. Click
Including a device connected to a communication module as a target
Some or all remote registers of a target device are used in a system while performing an iQ Sensor Solution function.
Therefore, add "Remote register use prohibited status (SW0160 to SW0163)" to the interlock when creating a program.
4 CC-Link
54
For details on the display methods of the "Network Parameter - CC-Link Module
Configuration" screen, refer to the following manual.
 GX Works2 Version 1 Operating Manual (Common)
1.
Click the [Operation Setting] button on the "Network Parameter - CC-Link Module
Configuration" screen.
2.
Select "Read Model Name of Slave Station" on the "Operation Setting" screen,
and click the [OK] button.
3.
Click the [End] button, and select [Online]  [Write to PLC].
1. Check
4.
Power OFF to ON or reset the CPU module.