Error code
Error and cause
480AH
• The function was performed for the CC-Link module whose
operation has been switched from the standby master station to
master station.
• The function was performed for the CC-Link IE Field Network
module whose operation has been switched from the sub-master
operating station to the master operating station.
480BH
• The function was performed for the CC-Link module to which
"Read Model Name of Slave Station" is not set in the setting of the
automatic detection function of connected devices.
• The function was performed for the CC-Link IE Field Network
module to which "Read Model Name of Slave Station" is not set in
the setting of the automatic detection function of connected
devices.
480CH
The specified command could not be executed because the iQ
Sensor Solution function (the automatic detection function of
connected devices) is processing.
480DH
• The specified command could not be executed because the iQ
Sensor Solution function (reflection function of the communication
setting) is processing.
• Communication timeout occurred to a command of the iQ Sensor
Solution function.
480EH
• The specified command could not be executed because the iQ
Sensor Solution function (the Sensor/Device Monitor function) is
processing.
• The specified command could not be executed because the iQ
Sensor Solution function (the sensor parameter read/write
function) is processing.
• Communication timeout occurred to a command of the iQ Sensor
Solution function.
4810H
The target module for the iQ Sensor Solution data restoration differs
from the module where the iQ Sensor Solution data backup was
performed.
4811H
The target module for the iQ Sensor Solution data restoration differs
from the module where the iQ Sensor Solution data backup was
performed last time.
4812H
The functions that cannot be performed simultaneously, such as the
file transfer function (FTP server/client), are being performed.

AnyWireASLINK

For details on the error codes, error information, error causes, and corrective actions, refer to the manual of the
AnyWireASLINK device used.
When using GX Works2, these information can be checked in the "Monitoring Information" window. (Page 32 Monitoring
Devices Supporting iQSS)

CC-Link

Mitsubishi Electric Corporation
Error code
Error and cause
BAD1H
Data backup failed.
BAD2H
Data restoration failed.
BC55H
CC-Link communication error
APPX
348
Appendix 5 Error Code List
Corrective action
Perform data backup again.
If RXnB turns ON when turning the power ON, the error is on the
hardware.
The restored data may be corrupted.
If RXnC turns ON when turning the power ON, the error is on the
hardware.
A communication error occurred.
Perform the data backup/restoration function again.
Corrective action
Turn OFF to ON the power of the mater station and standby master
station, and retry.
Select "Read Model Name of Slave Station" in the setting of the
automatic detection function of connected devices and retry.
Terminate the iQ Sensor Solution function (the automatic detection
function of connected devices) and retry.
• Terminate the iQ Sensor Solution function (communication
setting reflection) and retry.
• Review the value set to the communication time check in the
engineering tool.
• Retry after a while.
• Terminate the iQ Sensor Solution function (the sensor parameter
read/write function) and retry.
• Review the value set to the communication time check in the
engineering tool.
Perform data restoration to the module where data backup was
performed.
• Perform data backup to the module where data backup was
performed last time.
• Set a different folder number.
Retry after a while.
Type/model name
■Analog input module (Voltage/
Current input)
• AJ65SBT2B-64AD
■RTD analog input module
(Temperature input)
• AJ65SBT2B-64RD3
■Thermocouple analog input
module (Temperature input)
• AJ65SBT2B-64TD
■Analog output module (Voltage/
Current output)
• AJ65SBT2B-64DA