Mitsubishi Electric IQSS-R-E Reference Manual page 189

Iq sensor solution, melsec iq-r/iq-f/l/q series, got2000, melipc
Table of Contents

Advertisement

■Setting the restoration setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
Target module type
1H: AnyWireASLINK
2.
Setting an execution unit
Set a unit to specify the range of data to be restored at once.
Specify the execution unit to the upper 8 bits of SD1362.
Execution unit
1H: Module unit
2H: ID unit
3.
Selecting a folder for data restoration
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
Target folder
0 to 99: Target folder specification
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit, set a start I/O number to SD1364 (iQ Sensor Solution data backup/
restoration target setting (target module)).
In a multiple CPU system, only the AnyWireASLINK master module controlled by a host CPU can be backed up. Data backup
cannot be performed for non-controlled modules.
Target device (Module)
0 to FFH: Start I/O number
• Setting an ID number
When '2H' (ID unit) is set for the execution unit, set an ID number to SD1365 (iQ Sensor Solution data backup/restoration
target setting (target device 1)).
Target device (ID number)
0 to 9999: ID number
5.
Setting the operation setting when a data restoration error occurs
Set the operation to be performed when the data restoration fails on some devices while being processed to multiple devices
supporting iQSS to the lower 8 bits of SD1367 (iQ Sensor Solution data backup/restoration operation setting).
Operation on error
0H: Continue
1H: Stop
Description
Set this to specify a device supporting iQSS which is connected to the AnyWireASLINK master module.
Description
Set this to specify all devices supporting iQSS which are connected to the AnyWireASLINK master module with
the specified start I/O number.
Set this to specify the device supporting iQSS with the specified ID number among the devices which are
connected to the AnyWireASLINK master module with the specified start I/O number.
Description
Specify a number (0 to 99) of the backup folder name to be restored.
Description
Set the start I/O number (the value obtained by dividing the start I/O number by 16) of the AnyWireASLINK
master module which is connected to a target device supporting iQSS.
Description
Set the ID number of a target device supporting iQSS.
Description
Set this to continue a data restoration even if it fails on some devices.
Set this to stop a data restoration if it fails on some devices.
7.4 Backing up/Restoring Data of Devices Supporting iQSS