Points to be checked before data backup/restoration
■Check the availability of data backup/restoration
The data can be backed up and restored when a CC-Link IE Field Network master/local module and a bridge module
(NZ2AW1GFAL) satisfy the following conditions.
Perform the automatic address detection function and the parameter batch read function before data backup/restoration.
The 'n' indicates the address assigned to the master station by the station number setting.
Module
CC-Link IE Field Network master/local
module
Bridge module (NZ2AW1GFAL)
*1 Set the target station.
*2 Excluding when the error code is 0131H.
Considerations for data backup/restoration
■Stations to which data cannot be backed up and restored
The data backup and restoration function cannot be performed on the following stations.
• Local station
• Sub-master station that is monitoring the master station (performing the sub-master operation)
• Station whose data link has stopped due to a station number duplication error
• Station whose data link has stopped due to a station number out of range error
• Station whose network number is mismatched
■Use of an SD memory card
• During a data backup or restoration, do not perform the following actions: turning OFF the power, resetting a module, and
inserting or removing an SD memory card.
Otherwise, the data backup or restoration will be interrupted and the data will not be backed up or restored properly.
• Normal backup data cannot be created if the memory size or the number of files exceeds the maximum storage capacity of
an SD memory card during a data backup.
■Operations with a display unit during data backup
If any of the following operations are performed with a display unit during data backup, the operation will be completed
abnormally and the error is displayed on the display unit.
Operation name
Project data batch save/load function
File deletion on the "Memory card operation menu" screen of a display unit
Condition to be checked
Module error
Module READY
Host station data link status
*1
Other station data link status
Remote READY
DP/DN short error
Transmission cable voltage drop error
DP/DN disconnection error
Slave module alarm signal
Parameter access completion flag
Parameter access error
Automatic address detection flag
Remote device RX signal
Xn0
XnF
Xn1
SW00B0 to SW00B7
RXn0
RXn1
RXn3
RXn4
RX(n+1)0
RX(n+1)1
RX(n+1)2
RX(n+1)4
5.5 Backing up/Restoring Data of Devices Supporting iQSS
Signal status
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
*2
OFF
ON
OFF
OFF
5 CC-Link IE Field Network
5