SYSTEM CONFIGURATION
Steps for Configuring Defining an Alarm Queue
1. From the Alarm Qs screen, select the Alarm Number to configure.
2. Enter the Alarm Q Description.
3. Check the Enabled box to enable Monitor 1for the alarm queue. Then select the
4. If desired, enable and specify Monitors 2, 3, and 4.
5. If desired, enable and specify the Blank Source camera to be used when no alarm is
6. If desired, enable and specify a Keyboard to be used with this alarm queue.
7. Enter pertinent notes regarding the alarm queue in the Alarm Queue Notes field.
8. Select
An Example of the Usage of Alarm and Alarm Queue
Set alarm 1 enable, its Auto camera is Input 2, Accept Sequence is Sequence 3,
Default Message is Message 1, and Connect Close is Sequence 4, the sequence's
priority is 2, and in sequence 4 there is an ALARMQ function adds Alarm 1 into alarm
queue 1.
Set alarm 2 enable, its Auto camera is Input 3, Accept Sequence is Sequence 5,
Default Message is Message 2, and Connect Close is Sequence 6, the sequence's
priority is 3, and in sequence 6 there is an ALARMQ function adds Alarm 2 into alarm
queue 1.
Set alarm queue 1's Monitor 1 as Mon 1, Monitor 2 as Mon 2, Blank source as input 4,
Keyboard as K/B 1.
When Alarm 1 closes, the Sequence 4 starts, Alarm 1 is added into Alarm Queue 1, and
at the same time Input 2 switches to Mon 1, Message 1 is displayed on Mon 1. In another
word all the Alarm 1's actions works on Mon 1. K/B 1 will displays 'Q 1,Alarm 1'.
When Alarm 2 closes later, the Sequence 6 starts, Alarm 2 is added into Alarm Queue 1,
because alarm 2's priority is higher then Alarm 1 so Alarm 2's actions will work on Mon 1,
and Alarm 1's actions will work on Mon 2. K/B 1 will displays 'Q 1,Alarm 2'.
At this moment, presses key 'Alarm Ack' on K/B 1, Alarm 2 will be deleted from Alarm
Queue 1, Alarm 1's actions works on Mon 1, alarm queue 1's Blank source Input 4
switches to Mon 2. Alarm 1 Accept sequence 'sequence 3' starts.
Press key 'Alarm Ack' on K/B 1 again, Input 3 switches to Mon 2 will be deleted from
Alarm Queue 1, alarm queue 1's Blank source Input 4 switches to Mon 1. And the K/B 1
will display 'No active queue'. Alarm 2 Accept sequence 'sequence 5' starts.
76