Connecting Ac Power To The Cisco 10008 Router - Cisco 10008 Hardware Installation Manual

Hardware installation guide
Table of Contents

Advertisement

Connecting AC Power to the Cisco 10008 Router

Figure 3-21
Replace the rear safety cover, making sure that the power wires exit through the holes on the side of the
Step 11
cover
Go to the
Step 12
installation.

Connecting AC Power to the Cisco 10008 Router

The Cisco 10008 router can be powered directly from the facility VAC input through the AC PEM
(100-240VAC). The AC PEM is provided with an IEC 320 250V, 20A power cord with a male type
connector (16A rating for Europe) for the attachment of power cords used throughout the world.
The 20A connector on the AC PEM is incompatible with the 15A power strips that are used in most
Caution
equipment racks. Wiring codes prevent the AC-input power cable from being used with the power strips
in equipment racks.
The AC power cord that connects to the PEM power cord and then to the building VAC is not shipped
Note
with the Cisco 10008 router. You must order this power cord separately.