10.3 Commissioning - Honeywell ESSER FACP Technical Information

Table of Contents

Advertisement

Periphery components for ESSER FACP

10.3 Commissioning

The commissioning and maintenance must only be performed by qualified technicians who are familiar with the
fire alarm system.
The tools 8000 service and programming software is used for commissioning and performing maintenance on
the devices. All functions and the status are checked cyclically and transmitted to the panel during the test
operation of the FACP, where they are displayed in case of a fault.
Example:
1. Service PC with tools 8000 programming software to the FACP and set up panel configuration
2. Connect installed esserbus
3. Read bus device via wiring recognition
4. Assign IQ8Quad fire detector to the desired detector zone (e.g. zone 601/detector 1)
5. Define control zone number to activate the audible/optical alarm device
6. Create individual signal templates for audible alarm devices
7. Define audible devices as "local" in the properties dialogue box
8. Select and allot signal templates
9. Check and save customer data
The customer data that was configured using the service and programming software tools 8000
must correspond to the actual configuration of the ESSER FACP and the external periphery.
An IQ8Quad fire detector with voice output, such as the O²T/FSp multisensor detector
(Part No. 802385), can also output a warning tone to alert.
Depending on the number of integrated alarm devices, optical and/or audible, it may be necessary to programme
an additional one or two control zone numbers. The detector and control zone numbers must always relate to the
valid number interval of the local fire alarm control panel. It is not possible to activate integrated alarm devices of
the IQ8Quad fire detector across different panels.
Always observe the following system limits for assignment:
a maximum of 127 devices in 127 detector zones can be installed on one loop
a maximum of 32 devices can be aggregated into one detector zone
it is not possible to operate a combination of manual call points MCP and automatic detectors
esserbus
®
transponders always be aggregated into separate detector zones
68
®