Honeywell ESSER FACP Technical Information page 16

Table of Contents

Advertisement

Periphery components for ESSER FACP
Detector Specifications (not ATEX)
Rate-of-rise heat detector 803271.EX
Quiescent current @ 19 V DC
Ambient temperature
Specification
VdS approval
Declaration of performance
Optical smoke detector 803371.EX
Quiescent current @ 19 V DC
Ambient temperature
Specification
VdS approval
Declaration of performance
2
O
T-multisensor detector 803374.EX
Quiescent current @ 19 V DC
Ambient temperature
Specification
VdS approval
Declaration of performance
All values based on a temperature range of 25 °C.
The FACP emergency power capacity is determined using the programming software tools 8000
or via the calculation function available at www.esser-systems.com.
For further information, safety calculations and certifications, see Technical Information
798920.EU.xx.
EC-Type Examination acc. Construction Products Regulation (CPR)
*5
Ambient temperature of fire detector types for detailed system design
*6
Except "80337x.EX.F0" and "80337x.EX.NU"
16
*1
*1
/ 803271.EX.F0
:
40 µA
:
-20 °C ... +50 °C
*5
:
EN 54-5 A1R : 2000 / A1 : 2002
:
G 209223
:
DoP-20913130701
*2
*2
/ 803371.EX.F0
/ 803371.EX.NU
:
50 µA
:
-20 °C ... +70 °C
*5
:
EN 54-7 : 2006
:
G 209224
:
DoP-20914130701
*2
*2
/ 803374.EX.F0
:
60 µA
:
-20 °C ... +65 °C
*5
:
EN 54-7 : 2006 / -5 B : 2000 / A1 : 2002
:
G 209225
:
DoP-20915130701
*1
/ 803271.EX.NU
*2
/ 803371.EX.IN
*2
/ 803374.EX.NU
/ 803374.EX.IN
*6
, CEA 4021
*2
*2
TI 798960.GB0 / 04.20