Honeywell ESSER FACP Technical Information page 58

Table of Contents

Advertisement

Periphery components for ESSER FACP
Alarm device
807205R
807205W
807214RR
807214WW
807224RR
807224RW
807322R / -.SVxx
807322W / -.SVxx
807372RR.xx / .SVxx
807372RW.xx / .SVxx
The load factors, FACP battery capacity, etc. can be determined using the configuration tool at
www.esser-systems.com.
The "Maxpector VAD Selection Guide" is available at www.esser.maxpector.com for online planning
and configuration of the devices.
x
Fig. 40: W = wall mounting / signal range = height (x) x floor area (y x y)
Signal ranges  visual alarm (default setting)
Class
Classification
W: Wall /
W-x-y
O: open
W-2,4-5
W
W-3,2-7
W
W-3,6-8
W
OW-1,6-3,5
O
W2,4-5
W
W2,8-6
W
For further information on the sound pressure levels of the audible alarm, see Chap. 10.2.2 and 10.2.3.
58
Alarm
Visual Audible Speech
---
---
---
---
---
---
W / O
y
Installation
Room width /
height
depth
y [m]
x [m]
2,4
5
3,2
7
3,6
8
1,6
3,5
2,4
5
2,8
6
Load factor
Visual
(incl. Speech)
---
---
---
---
---
3,0-7,9
---
3,0-7,9
---
3,0-7,9
---
3,0-7,9
---
---
3,0-7,9
3,0-7,9
y
Light color
Flash rate
r: red /
[Hz]
w: white
r / w
0,5
r / w
0,5
r / w
0,5
r / w
1
r / w
1
r / w
1
Audible
Total
1,5-3,0
1,5-3,0
1,5-3,0
1,5-3,0
---
3,0-7,9
---
3,0-7,9
1,5-3,0
4,5-10,9
1,5-3,0
4,5-10,9
4,0
4,0
4,0
4,0
4,0
7,0-11,9
4,0
7,0-11,9
Effective
Load factor
Max. Number
intensity
(LF)
6,6
3
13
6,2
17
7,9
3,2
3
6,6
5,5
9,6
9,9
TI 798960.GB0 / 04.20
max.
Number
per loop
64
64
32
32
21
21
24
24
13
13
of devices
32
15
12
32
17
12