Conventional Alarm Device - Honeywell ESSER FACP Technical Information

Table of Contents

Advertisement

Wiring
The alarm device is connected directly to the esserbus
lines of the connection cable should not be lie in the same cable or installation tube. Cable shielding of the
connection protects the signal lines from the effects of disturbances.
Meldersockel / Detector base
805590
EP6
OUT5
IN4
C3
A -
A +
B -
B +
Fig. 41: Wiring example esserbus
Commissioning
The devices can be operated with the factory settings. Alternatively, the object-specific configuration is possible
with the service and programming software tools 8000.
With an audible alarm, up to four different audible signals incl. an alarm signal and an evacuation signal can
be selected.
With a visual alarm, it is possible to configure various signal ranges (with FACP FlexES Control and tools
8000 from V1.24).
With voice functionality, voice outputs can also be configured for the audible and visual signals. The DIN
tone is set as the default signal.
Depending on the device type used and the FACP programming, the range of audible signals, visual signals
and voice outputs available may be limited. The load factor is depending on the selected configuration.
Special versions (Part No. 807xxx.SVxx)
The acoustic signals for alarms and evacuation are programmed for specific customers and objects at the
factory and may therefore differ from the stated data.
The IQ8Alarm Plus alarm devices emit very bright flashes of light as a visual alarm. For configurations
of very large signal ranges in particular, the flashes of light have a very high intensity level.
The planner/fire alarm specialist must be aware of the dangers and instruct people accordingly in
advance:
Extremely bright LED are integrated into the alarm devices and are activated in the event of an
alarm.
Only work on the device when it is disconnected from the power supply.
There is a risk of blindness – do not look directly into the light!
9.2

Conventional alarm device

There is a wide range of conventional alarm devices (visual, acoustic, combined) available in the Fire Alarm
Technology product group catalogue. These devices are generally connected to ESSER fire alarm control
panels via esserbus
®
transponders (refer to Section 12).
TI 798960.GB0 / 04.20
Meldersockel / Detector base
805590
+
max. 100 m
Option
1
EP6
1
OUT5
EM2
EM2
IN4
C3
®
PLus
Periphery components for ESSER FACP
®
PLus. Further wiring is not necessary. Outward and return
Signalgeber /
Alarm device
+C
+C
-IN -OUT
-
Signalgeber /
Alarm device
+C
+C
-IN -OUT
B -
B +
61