Periphery components for ESSER FACP
12.6 esserbus
®
The esserbus
®
transponder Standard Interface Extinguishing (SIE) allows for the connection of extinguishing
agent control systems/extinguishing systems to the fire alarm system.
An external power supply of 12 V DC or 24 V DC can be connected to the esserbus
For 12 V DC operation, the power converter (Part No. 781336) is required. The external power supply can be
configured to be monitored using the service and programming software tools 8000.
Fig. 52: esserbus
®
-Koppler SIE
Specifications
Loop
Rated voltage
Current consumption
External power supply
Operating voltage
Current consumption
Quiescent current
Zone inputs
Rated voltage
Current consumption
Length of connection cable
Relays
Contact rating
Ambient temperature
Storage temperature
Humidity
Protection rating
Weight
Dimensions (w x h x d)
Specification
VdS approval
Declaration of Performance
For further information and accessories refer to product catalogue and documentation of the devices.
84
transponder SIE (Part No. 808613.30)
:
19 V DC, max. 42 V DC
:
approx. 250 µA @ 19 V DC
:
10 V DC ... 28 V DC
:
max. 120 mA @ 12 V DC
:
approx. 10 mA @ 12 V DC
:
9 V DC
:
max. 25 mA
:
max. 1.000 m
:
30 V DC / 1 A
:
-10 °C ... +50 °C
:
-25 °C ... +75 °C
:
≤ 95% rel. humidity (no condensation)
:
IP 40 (in housing)
:
approx. 28 g
:
82 x 72 x 20 (mm)
:
EN 54-17:2005 / -18:2005
:
G 206042
:
DoP-20614130701
Features
Only one loop address is needed per transponder
Max. 100 transponders per FACP
Max. 31 transponders per loop
Max. 32 transponders per detector zone
®
transponder.
TI 798960.GB0 / 04.20