Loop-participants and load factors
Fire detector IQ8Quad with integrated alarm devices
Part No.
802382
802383
802384
802385.xx
802386.xx
Alarm device IQ8Alarm Plus
Part No.
807205R
807205W
807214RR
807214WW
807224RR
807224RW
807322R / -.SVxx
807322W / -.SVxx
807372RR.xx / .SVxx
807372RW.xx / .SVxx
The load factors, FACP battery capacity, etc. can be determined using the configuration tool at
www.esser-systems.com.
TI 798960.GB0 / 04.20
Description / function / device type
O/So optical smoke detector
O²T/F multisensor detector
O²T/So multisensor detector
O²T/FSp multisensor detector
O²T/Sp multisensor detector
Alarm
Visual Audible Speech
---
---
---
---
---
---
---
---
---
---
---
---
Periphery components for ESSER FACP
Load factor
Audible
Visual
(incl. Speech)
---
1,5-3,0
---
1,5-3,0
3,0-7,9
---
3,0-7,9
---
3,0-7,9
1,5-3,0
3,0-7,9
1,5-3,0
---
4,0
---
4,0
3,0-7,9
4,0
3,0-7,9
4,0
Load factor
2
2
2
3
3
max.
Number
Total
per loop
64
1,5-3,0
64
1,5-3,0
32
3,0-7,9
32
3,0-7,9
21
4,5-10,9
21
4,5-10,9
24
4,0
24
4,0
13
7,0-11,9
13
7,0-11,9
77