Honeywell ESSER FACP Technical Information page 23

Table of Contents

Advertisement

Part No.
Detector type
*1
800171
Fixed heat detector
800177
*1
Fixed heat detector
Rate-of-rise heat
800271
*1
detector
*2
800371
Optical smoke detector
800374
*2
O
2
T multisensor detector
OT
blue
multisensor
800375
*2
detector
OT
blue
-LKM-multisensor
*2
800379
detector
*1
Head sensor type
*2
Smoke
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.
For further information refer to product catalogue.
TI 798960.GB0 / 04.20
Specific detector specifications
Quiescent current @ 9 V DC : 25 µA
Usage temperature
Specification
VdS approval
Declaration of Performance
Quiescent current @ 9 V DC : 25 µA
Usage temperature
Specification
VdS approval
Declaration of Performance
Quiescent current @ 9 V DC : 25 µA
Usage temperature
Specification
VdS approval
Declaration of Performance
Quiescent current @ 9 V DC : 30 µA
Usage temperature
Specification
VdS approval
Declaration of Performance
Quiescent current @ 9 V DC : 60 µA
Usage temperature
Specification
4021
VdS approval
Declaration of Performance
Operating voltage
Quiescent current @ 9 V DC : 50 µA
Usage temperature
Specification
4021
VdS approval
Declaration of Performance
Operating voltage
Quiescent current @ 9 V DC : 35 µA
Air velocity range
Ambient temperature
Specification
VdS approval
Declaration of Performance
Periphery components for ESSER FACP
*3
: -20 °C ... +50 °C
: EN 54-5 A1S : 2002
: G 213068
: DoP-21291131101
: -20 °C ... +65 °C
: EN 54-5 BS : 2000
: G 213067
: DoP-21295131101
: -20 °C ... +50 °C
: EN 54-5 A1R : 2002
: G 213069
: DoP-21293131101
: -20 °C ... +72 °C
: EN 54-7 : 2006
: G 213066
: DoP-21296131101
: -20 °C ... +65 °C
: EN 54-7 : 2006/-5 B : 2000, CEA
: G 213070
: DoP-21296131101
: 9 V DC ... 42 V DC
: -20 °C ... +50 °C
: EN 54-7 : 2006/-5 A2 : 2002, CEA
: G 213065
: DoP-21298131101
: 9 V DC ... 42 V DC
: 1 ... 20 m/s
: -20 °C ... +50 °C
: EN 54-27 : 2015
: pending
: ---
23

Advertisement

Table of Contents