12.7 esserbus
®
The IQ8FCT XS can be used as a fire control transponder (FCT) for controlling and monitoring fire protection
equipment* such as fire dampers, as well as a technical alarm module (TAL) for monitoring an external switching
contact. The transponder is a loop device and therefore has an integrated loop isolator, a contact input and a
potential-free relay output. For external indication, a parallel detector indicator (Part No. 781804, 781814 or
801824) can be connected (max. loop length 100 m). The transponder does not require a separate power supply.
To monitor the contact, the alarm and monitoring module (Part No. 804870) or an external resistance combination
can be used. The max. loop length to the contact is 500 m.
* Observe the local and regional requirements/regulations for the activation of fire protection equipment.
Fig. 53: esserbus
®
transponder IQ8FCT XS
In order to control the fire protection device in compliance with the relevant standards, the IQ8FCT
should be installed right next to or inside the control device.
Specifications
Loop
- Nominal voltage
- Quiescent current
- Alarm current
Number
Alarm indicator
Operation indicator
Connection terminals
Application temperature
Storage temperature
Humidity
Protection rating
Housing
Colour
Weight
Dimensions (w x h x d)
- IQ8FCT XS
- M200SMB
Specification
VdS approval
Declaration of Performance
For further information and accessories refer to product catalogue and documentation of the devices.
TI 798960.GB0 / 04.20
transponder IQ8FCT XS (Part No. 808606)
Features
Max. 127 transponders per ring loop
One contact input and one potential-free relay output
Connection for a parallel detector indicator
Power supply via fieldbus
Programmable impulse control of the relay output
Programmable runtime monitoring for activation of fire dampers
Programmable relay output NO/NC
Programmable impulse length for relay activation
(for time-limited activation)
Feedback input for monitoring fire control systems
Integrated loop isolator
Pluggable connecting terminals
Installation on top-hat rails or in surface mount housing
(Part No. M200SMB/SMB6-V0)
:
14 V DC ... 42 V DC
:
approx. 45 µA @ 19 V DC
:
approx. 9 mA @ 19 V DC, pulsed
:
max. 127 piece per loop
:
red LED
:
green LED
:
max. 2,5 mm² (AWG 26-14)
:
-20 °C ... +70 °C
:
-30 °C ... +75 °C
:
≤ 95 % rel. humidity (non-condensing)
:
IP 30 / IP 50 (with M200E-SMB-KO)
:
PC/ASA plastic
:
grey (similar RAL 7035)
:
approx. 90 g
:
90 x 93 x 23 (mm)
:
144 x 134 x 50 (mm)
:
EN 54-17 : 2005 / -18 : 2005
:
G 209138
: