Honeywell ESSER FACP Technical Information page 48

Table of Contents

Advertisement

Periphery components for ESSER FACP
7.1.1 Features and system limitations IQ8Wireless transponder
Possible operating modes
Stand-alone
Connection to a standard detection zone of a fire alarm control panel
Connection to the esserbus
System limits
Max. 32 IQ8Wireless detector bases (incl. IQ8Quad fire detector) per transponder or
Maximum 10 IQ8MCP / Manual Call Points (incl. IQ8Wireless Interface) per transponder.
If the IQ8Wireless transponder is connected to a conventional detector zone, all assigned IQ8Wireless devices
form one common detector zone (refer to VdS Guidelines)
System limits for the loop
An IQ8Wireless transponder is a device on the loop and requires 1 address
An assigned IQ8Wireless detector base (incl. IQ8Quad fire detector) is a device on the loop and requires
1 address
An IQ8Wireless MCP (incl. IQ8Wireless Interface) is a device on the loop and requires 1 address
An IQ8MCP (incl. IQ8Wireless Interface) is a device on the loop and requires 1 address
Max. 127 devices (addresses) per loop
Max. 10 IQ8Wireless transponders per loop
Every automatic IQ8Quad fire detector (with IQ8Wireless detector base) or IQ8MCP / Manual Call Points
(incl. IQ8Wireless Interface) can be configured as a separate detector zone
Automatic fire detectors and MCPs may not be operated on one and the same IQ8Wireless
§
transponder.
In practice, for each loop this means
Max. 123 IQ8Wireless bases (incl.IQ8Quad fire detectors without integrated alarm device), divided between
4 IQ8Wireless transponders or
Max. 117 IQ8Wireless bases (incl. IQ8Quad fire detectors without integrated alarm device), divided between
10 IQ8Wireless transponders
In addition to this, when using the maximum number allowed, no additional Wireless or bus devices can be
connected to the loop.
If additional bus devices such as detectors or esserbus
corresponding number of Wireless devices is reduced.
For further information refer to documentation of the IQ8Wireless devices.
48
®
®
or esserbus
PLus
®
transponders are operated on the loop, the
TI 798960.GB0 / 04.20