Specifications
Operating voltage
Batteries
Batteries lifetime
Current consumption
Frequency band
Transmission power
Range
Usage temperature
Storage temperature - without batteries
- with batteries
Humidity
IP rating
Material
Colour
Weight
Dimensions (∅ x H)
Specification
VdS approval
Declaration of Performance
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.
52
: 8 V DC to 42 V DC
: 4 batteries per 3.6 V (AA)
: approx. 3 years
: 400 µA up to max. 2.5 mA
: 433/868 MHz
: max. 10 mW
: to max. 300 m
: -5 °C ... +55 °C
:
-20 °C ... +70 °C
+25 °C ± 10 °C
:
: ≤ 95% rel. humidity (non-condensing)
: IP 42
: ABS-V0
: white (similar to RAL 9010)
: approx. 265 g (incl. batteries)
: ∅ 135 mm x 88 mm, incl. fire detector
: EN 54-17 : 2005 / -18 : 2005 / -25 : 2008
: G 206091
: DoP-20620140331