Honeywell ESSER FACP Technical Information page 69

Table of Contents

Advertisement

In order to keep the total number of control zone numbers in complex security areas to a minimum, they can be
aggregated into a single one. Observe that the same type of alarm devices may be aggregated in this way.
In this way it is possible to activate all integrated audible and optical alarm devices with just one control zone
number.
Up to 32 control zones can be aggregated into one single control zone for multiple use. Control zones of the
esserbus
®
transponder cannot be aggregated into one zone.
FACP
Fig. 44: Example control zones
Device
Description
IQ8Quad fire
detector with alarm
IQ8Quad
esserbus
transponder
IQ8 Alarm Plus
TI 798960.GB0 / 04.20
601 / 2
601 / 1
St.-Grp.: 607 - audible alarm device
St.-Grp.: 608 - optial alarm device
esserbus
602 / 4
602 / 3
Detector zone
601
device
602
MCP
®
603
604
Periphery components for ESSER FACP
601 / 3
PLus
®
602 / 1
602 / 2
Detector no.
1
2 ... 4
1 ... 4
1 ... 4
1 ... 2
601 / 4
604 / 1
604 / 2
603 / 3
603 / 4
Control zone
Alarm device
607
audible
608
---
---
---
---
603 / 1
603 / 2
visual
69