7.6

Standardized Interface - Extinguishing

With this application it is possible to realize standardized interface >extinguishing< in accordance to the
VdS 2540 requirements for Extinguishing control systems.
Fire Alarm Control Panel
Extinguishing
command
Fault extinguishing system
Extinguishing system
triggered released
Fig. 45: Wiring of the interface - Extinguishing
The Inputs and Outputs are used as follows:
Input >Extinguishing<
A free selectable automatic detector zone MG1 toMG8 of the LMST 8010 must be programmed as >Standard-
zone-Extinguishing<. The chosen detector zone is only operable with this assigned function.
Output >Failure extinguishing system<
A free selectable relay 1 to 8 of the LMST 8010 must be programmed with the corresponding jumpers as >not
monitored< and configured in the customer data with the status function >Fault<. Connect required resistors R1
and R2 (refer to fig. 45).
Output >Extinguishing system triggered<
A free selectable relay 1-8 of the LMST 8010 must be programmed with the corresponding jumpers as >not
monitored< and configured in the customer data with the status function >Extinguishing system triggered<.
Connect required resistors R3 and R4 (refer to fig. 45).
According to VdS Guideline 2540, the terminal strips in the FACP and in LMST 8010 must be
labelled according to their respective function.
FB 798955.GB0 / 09.07
Extinguishing Control Computer 8010 – 19-Inch
Extinguishing control
R1
R2
R3
R4
system 8010
Automatic detector zone
Relay output A
Relay output B
61