Cpu-Failure Mode - Honeywell ESSER 8010 Operation And Installation Instructions Manual

Extinguishing control computer
Hide thumbs Also See for ESSER 8010:
Table of Contents

Advertisement

8.2

CPU-failure mode

Even in the CPU-failure mode, e.g. failure of the main processor or a trouble in the program memory, the alarm
and triggering functions of the Extinguishing Control Computer can be guaranteed through the >Emergency
operation trouble< and >Emergency operation fire< mode.
For this purpose, the function >Emergency operation fire< (relay 10) and >Emergency operation trouble<
(relay 11) must be configured with the corresponding jumpers.
In CPU-failure mode, all relays are de-energized and change the switching state except the relay >Emergency
Operation Trouble< (relay 11). The red display and control panel LED >Emergency operation< is permanently
activated.
Installed and operational detector zones continue to be monitored for the status >Fire<. If a fire is detected, the
relay >Emergency Operation Fire< (relay 10) changes the switching state.
Connection example (Relay terminal card type "Phoenix")
45
44
43
42
Relay 11
Fig. 46: Jumper for emergency mode settings (relay 10 and 11)
Relay 10
>Emergency operation fire< or Standard function,
configured with jumper J7
Relay 11
>Emergency operation trouble< or Standard function,
configured with jumper J5
FB 798955.GB0 / 09.07
39
41
40
Relay 10
Extinguishing Control Computer 8010 – 19-Inch
REL10
REL11
Emergency operation
trouble
inactive active
J5
F2
F3
Emergency
operation
F4
Emergency operation
fire
inactive active
J7
Changeover contact,
contact rating
max. 30 V DC / 2A
65