Extinguishing Control Computer 8010 – 19-Inch
4.3

Installation information

The Extinguishing Control Computer 8010 – 19-Inch and 19-inch cabinet with safety glass and safety lock can
be purchased without installations for self-assembly (Part No. 769163) or as a complete, pre-mounted and
ready-to-connect product (Part No. 769164).
The increased mechanical protection of the 19-inch cabinet also makes it suitable for use in industrial
production facilities.
If the 19-inch installation/cabinet is assembled by the installation company, the installation company
automatically becomes the manufacturer of the systems with all rights and obligations according to
DIN ISO 900x and all the relevant standards and guidelines.
Fire alarm systems and other system components such as ELA technology must not be installed
together in one cabinet.
Ambient conditions
The ambient conditions for the assembly location and surfaces must comply with Class 3k5 according to DIN
EN 60721-3-3.
Assembly location and assembly surface
The 19-inch installations and cabinets with fire alarm control panels may be installed only in dry, clean,
conditionally accessible and adequately lit rooms. If several fire alarm control panels are to be assembled in one
enclosed 19-inch cabinet, the maximum bearing strength (Kg/m²) of the floor may have to be considered (e.g.
pile floors).
To prevent the 19-inch cabinet becoming top heavy when the pivot frame is open, fix it to a suitable wall.
The fire alarm system must not be installed in facilities with damaging influences. Parts of the fire alarm system
may be fed through these facilities if the requirements of the DIN VDE 0800 series are fulfilled.
Assembly material
The panel must be installed with suitable fixing material (screws, threaded bolts) with no mechanical stress on
the assembly surface of the 19-inch cabinet. The panel may be operated only when it has been properly
installed on the surface with sufficient bearing power.
Installation height of the operating modules and optical displays
Operating modules and optical displays should be installed between 800mm and 1,800mm above the place
where the operator stands.
Energy supply
The fire alarm system is not suitable for connection to an IT voltage supply system.
Disturbance variables
Avoid electrical and mechanical disturbance variables. This applies especially to the installation of panels,
components and installation cables in the direct vicinity of fluorescent lamps or energy cables and mounting on
vibrating, unstable surfaces such as thin partition walls.
Cabinet ventilation
The ambient conditions for the assembly/operation of the fire alarm system must comply with Class 3k5
according to IEC 721-3-3:1994. If these climatic conditions cannot be fulfilled, appropriate countermeasures
must be taken.
If you believe that the ambient temperature is unsuitable for the installed devices, you must take appropriate
measures to air-condition the 19-inch cabinet.
In principle you must prevent heat accumulation between the installed devices and between the devices and the
walls of the 19-inch cabinet. Especially ensure that there is an adequate heat buffer between the highest
installed panel and the top of the 19-inch cabinet.
Door contact
The 19-inch cabinet is fitted with an electrical door contact that monitors when the door is opened. This door
contact may be used in fire alarm control panels to switch off the master box (MB) of one or more panels.
24
FB 798955.GB0 / 09.07