Extinguishing Control Computer 8010 – 19-Inch
Technical Alarm Modules series 9200 / IQ8TAM (only LMST 8010 - series 3)
Required operation mode programming
Connection of max. 30 technical alarm modules (with isolator) or IQ8TAM-modules per detector zone.
Detector zone X
+
-
External dry contacts (only LMST 8010 - series 3)
Required operation mode programming
The connection of external dry contacts to a detector zone input is possible. At this it must be observed that the
detector zone is terminated with a 4,7k Ω End-of-line resistor in the last device of the zone.
Detector zone X
+
-
42
®
esserbus
zone
Conventional zone
4K7
FB 798955.GB0 / 09.07