7.3

Zone board - series 3

The zone board - series 3 is designed for connection of 13 detector zones. Terminals 1 to 8 are suitable to
connect automatic detectors and/or series 9200 / IQ8Quad (without alarm devices), technical alarm modules, as
®
well as esserbus
transponders in order to control further external peripherals. Five technical zones 9 to 13 are
available for non-automatic detectors (manual call points, push-button controls) and inputs for connecting
external dry contacts. The detector zones are configured for connection of automatic fire detectors, and/or
technical alarm modules, or esserbus
X2
N
PE
L1
TRAFO PRIMARY
F2
X5
X1
T1A
F1
T4A
X3
X4
Fig. 29: Zone board series 3 (Part No. 771789) / position of the subassemblies
Terminals
The zone board is fully internal connected with the terminals of the mains supply voltage and the D-SUB board
of the external terminal card connection.
Unused alarm zones should be programmed as >unused< in the customer data or fitted with a
terminating resistor 4,7 K Ohm.
Do not connect fire detectors or technical alarm modules series 9000 / 9100.
Mixed operation of automatic fire detectors, and/or technical alarm modules or esserbus
transponders in a common detector zone is not permitted.
FB 798955.GB0 / 09.07
®
transponders via the programming software LKDE from Version V02.00.
Connection prozessor card
Extinguishing Control Computer 8010 – 19-Inch
X16
Zone board
Internal connection
to zone terminals
J9
Groung fault
identification
®
39