Extinguishing control computer
Hide thumbs Also See for ESSER 8010:
Table of Contents

Advertisement

Emergency Stop (yellow LED)
On
An already triggered extinguishing procedure is stopped during the evacuation time by the
Emergency Stop zone 10.
An emergency stop button of this technical zone has been pressed.
Switch-off (yellow LED)
On
Common disablement, at least one disablement was recognized.
Test operation (yellow LED)
On
The test operation of an detector zone was activated.
The Test Mode function can only be activated one automatic detector zone no.1-8 at the same
time.
Flashes
The revision mode for outputs has been activated. The function >Revision mode< is activated for
all outputs which have been programmed with the revision function.
Revision mode always has priority over the test mode in the display!
Extra releasing (green LED)
On
The LED indicates that the post-flooding has been triggered by the manual detector zone
(if configured as a common detector zone) or the extra released zone no. 11 has been activated
after the flooding time.
Outputs (green LED)
On
Indicates that an output has been triggered.
Additional information is given by the yellow LED in the status display of the outputs.
Alarm (red LED)
On
Common fire
FB 798955.GB0 / 09.07
at least one fire message was detected.
Extinguishing Control Computer 8010 – 19-Inch