Extinguishing Control Computer 8010 – 19-Inch
6.1

Emergency power supply

In case of loss of the mains voltage the control panel will be powered without a interruption by the connected
battery. Depending on the capacity of the battery a backup time of up to 72 hours can be realised. After that
time the external alarm devices must be still operable in an alarm condition. The activation of these devices
must be still possible with a minimum battery voltage of 21,2V DC.
For an emergency back-up time of 72 hours with the max. battery capacity a current of max. 230 mA is available
to power external loads.
F15
Battery 1
-
+
Battery 2
F14
Battery1
Fig. 24: Position and polarity of the battery terminals on the Power supply and relay board
The batteries must be mounted in the appropriate place inside the housing of the Extinguishing
Control Computer. Observe the required orientation of the battery placement (refer to battery label).
The connection of external batteries, e.g. placed on the cabinets floor is not permitted.
In case of the final discharging voltage of the batteries a max. voltage of 21,2 V DC is available to
supply and activate the valves. The valves must match this application requirements.
32
-
+
Battery2
FB 798955.GB0 / 09.07