Extinguishing control computer
Hide thumbs Also See for ESSER 8010:
Table of Contents

Advertisement

Automatic Fire alarm detectors series 9200 / IQ8Quad (only LMST 8010 - series 3)
Connection of max. 30. automatic Fire alarm detectors series 9200 (with integrated isolator in the detector base)
or 30 Fire alarm detectors IQ8Quad without alarm device (isolator integrated by factory default) per detector
zone.
Detector zone X
+
-
Only fire alarm detectors series 9000 could be connected to the detector zone inputs 1 to 8 of
the Extinguishing Control Computer 8010 - series 2 .
®
esserbus
transponder (only LMST 8010 - series 3)
Required operation mode programming
Connection of max. 30 esserbus
of outputs must not exceed 1000 outputs per Extinguishing Control Computer. Connected esserbus
transponders must be programmed as an esserbus
Detector zone X
+
-
Connectable esserbus
Part No. 808610 / 808610.10
Part No. 808611 / 808611.10
FB 798955.GB0 / 09.07
esserbus
®
transponders (with isolator board) per detector zone input. The total number
®
transponders:
®
esserbus
transponder 12 relays
®
esserbus
transponder 32 Optocoupler
Extinguishing Control Computer 8010 – 19-Inch
®
-zone
®
zone in the customer data.
®