Extinguishing Control Computer 8010 – 19-Inch
7.2

Zone board - series 2

The zone board - series 2 is designed for connection of eight standard detector zones for automatic detectors
series 9000 and/or 9100. Refer to section 7.4.5 for additional options to connect technical alarm zones.
The alarm zone operating mode (standard or EDD) is set via the associated jumpers (J1 to J8). Mixed operation
on one alarm zone of series 9000 and 9100 automatic fire detectors is not permissible.
X2
N
PE
L1
TRAFO PRIMARY
F2
X5
X1
T1A
F1
T4A
X3
X4
Fig. 27: Zone board - series 2 (Part No. 771793) / position of the subassemblies
Terminals
The zone board is fully internal connected with the terminals of the mains supply voltage and the D-SUB board
of the external terminal card connection.
Unused detector zone inputs must be programmed as >unused< in the customer data or
alternatively terminated with an End-of-line resistor.
Do not connect Fire detectors series 9200 / IQ8Quad.
Mixed operation of automatic fire detectors, and/or technical alarm modules or esserbus
transponders in a common detector zone is not permitted.
When connecting the mains voltage and the protective earth, refer to the instructions in the chapter
"Mains connection and earthing"!
36
Connection processor card
Std.
Std.
EDD
EDD
X16
Zone board
Std.
Std.
Std.
Std.
EDD
EDD
EDD
EDD
J9
Groung fault
identification
Std.
Std.
EDD
EDD
Internal connection
to zone terminals
FB 798955.GB0 / 09.07
®