Extinguishing Control Computer 8010 – 19-Inch
2.5

Connect / disconnect relay outputs

The relay outputs No. 1–13 can be switched on or off via the function keys and the 10-button keypad of the
control panel.
Unlocked
In operation
Example: Switching off relay output No. 7
In operation
Extinguishing system
activated
Extinguishing system
enabled
Output
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Fig. 9: Indication and Operation – Switching off relay output No. 7
The deactivated relay output is shown in the zone display with the continuously yellow LED. The green LED
>Outputs< also lights up to indicate that the zone display is showing the status of the outputs.
The zone display can be switched between the display of the 13 zones and of the 13 control outputs with the
function key >Switchover<. If the keypad is locked, the status of the zones is always automatically shown, even
if outputs have been deactivated.
Example: Switching on the relay output No. 7
In operation
Extinguishing system
activated
Extinguishing system
enabled
Output
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Fig. 10: Indication and Operation – Switching on the relay output No. 7
The continuously illuminated LED in the status display of the output turns out. The relay output is switched on
and will be activated in the case of an event.
Deactivated outputs will not notify an alarm message in case of a fire!
14
For operation, it is necessary to enable the keypad via the key-switch.
In operation
Extinguishing system
activated
Extinguishing system
enabled
Off
7
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
In operation
Extinguishing system
activated
Extinguishing system
enabled
On
7
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Detector zone
1
2
3
4
5
6
7
8
9 10 11 12 13
Fire/Switch off/Trouble
Detector zone
1
2
3
4
5
6
7
8
9 10 11 12 13
Fire/Switch off/Trouble