Extinguishing Control Computer 8010 – 19-Inch

7.4.1 Zone-terminal card (type Phoenix / Weco)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Fig. 32: External C-rail terminal card for zone inputs (manufacturer Phoenix / Weco)
Terminal
No.
1
Detector zone DZ1-
2
Detector zone DZ1+
3
Detector zone DZ2-
4
Detector zone DZ2+
5
Detector zone DZ3-
6
Detector zone DZ3+
7
Detector zone DZ4-
Detector zone DZ4+
8
9
Detector zone DZ5-
10
Detector zone DZ5+
11
Detector zone DZ6-
12
Detector zone DZ6+
13
Shielding
Shielding
14
15
Detector zone DZ7-
16
Detector zone DZ7+
17
Detector zone DZ8-
18
Detector zone DZ8+
19
Shielding
20
Shielding
21
esserbus UL- in
22
esserbus UL+ in
23
esserbus UL- out
24
esserbus UL+ out
25
Shielding
26
Shielding
44
Terminal
No.
27
Shielding
28
Shielding
29
DZ9- (manual alarm)
30
DZ9+ (manual alarm)
31
DZ10- (emergency stop)
32
DZ10+ (emergency stop)
33
Shielding
Shielding
34
35
DZ11- (extra release)
36
DZ11+ (extra release)
37
DZ12- (blocking)
38
DZ12+ (blocking)
39
DZ13- (failure extinguishing system)
DZ13+ (failure extinguishing system)
40
41
DZ14- (buzzer off)
42
DZ14+ (buzzer off)
43
DZ15- (reset)
44
DZ15+ (reset)
45
Shielding
46
Shielding
47
Battery 1- (of an external battery)
48
Battery 2- (of an external battery)
49
Battery 1+ (of an external battery)
50
Battery 2+ (of an external battery)
Shielding
Shielding
FB 798955.GB0 / 09.07